Mist Collector Sizing Guide
Machine Tool Enclosure Sizing Guide
When determining the sizing of mist collectors, several factors come into play. As a rule of thumb, we suggest multiplying the machine enclosure volume by a factor of 2-6 depending on the mist level, with a factor of 2 suitable for large machines of 1000 cubic feet and above.
Condition | Multiplier (X) | Formula |
---|---|---|
Light Mist | 1 to 2 | L x W x H x Multiplier = Required CFM |
Moderate Mist | 3 to 4 | L x W x H x Multiplier = Required CFM |
Heavy Mist / Smoke | 4 to 6 | L x W x H x Multiplier = Required CFM |
Example: On a lathe with high-pressure coolant and an internal dimension of 5ft high X 6ft deep X 10ft long, the machine enclosure is 300 cubic feet—the calculation suggests an airflow requirement of approximately 900 CFM, when multiplied by a factor of 3.